PSDX7-63 Miniature DC Circuit Breaker

Short Description:


Product Detail

Product Tags

GENERAL

PSDX7-63Z series DC miniature circuit breaker is used for DC voltage to 1000V, rated current to 63A circuitfor overload and short circuit protection, which can also be used as infrequent operation and transformation. The breaker is suitable for communication, photovoltaic system and other applications, such as DC system. Products comply with: GB 14048.2, IEC 60947-2 European Union RoHS environmental protection requirements Access to CCC, CB certifications

14
15

Application

PSDX7-63Z miniature DC circuit breaker is mainly used for DC rated voltage up to 1000V, overload and short circuit protection of current 63A DC electrical circuit and equipment. PSDX7-63Z miniature DC circuit breaker can also be used for the solar energy photovoltaic power generation system, the working voltage can be up to DC 1000V, which can rapidly break the DC fault of DC power distribution system; an important device ofthe solar powersystem - PV module can be protected from the reverse current from DC side and the hazard of feedback current from the AC side due to failure of inverter, to ensure the reliable operation of solar photovoltaic energy system.

16

Model and Meaning

Work Environment and Installation Conditions

1

◆ Ambient temperature : -35℃ 70

◆ Relative humidity: ≤95%

◆ Pollution level: class 2

◆ Elevation : ≤2000m

Specification Parameters

2

Main Parameters and Technical Performance

◆ Main Classifications

1. According to the rated current(In)

2. According to the pole numbers: 1P, 2P, 3P, 4P

3. According to the instantaneous tripping pattern: C Type (8~12)In : 1A, 2A, 3A, 4A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A

◆ Technical Parameters

1. Rated short circuit capacity

3

2. Mechanical and electrical life (times)

a. Electrical life (times): 8000

b. Mechanical life (times): 20000

3. Over Current Protection Feature under the Condition of (28~32)℃ Environment Temperature

4

Note: a term “cold state” refers to the condition without load before test under benchmark calibration temperature.

4. Rated impulse withstand voltage: 4kV

◆ Current correction for different ambient temperature

5

◆ Current correction coefficient at different elevations

6

◆ 2 Wiring: Suitable for 25mm wire connection, terminal tightening torque is 2.5N.m

◆ Power consumption of per pole

7
8

◆ Table 1 for tripping characteristic curve

◆ Product characteristics

9

1. Superior breaking capacity.

2. Double wiring function of wire and busbar.

3. Storage energy operation, fast closing, long lifetime.

4. Convenient installation and disassembly.

5. On-off instruction of contacts, improved safety performance.

6. Green environmental protection and energy saving.

Wiring Method

10

◆ Wiring diagram instructions

1. Power supply positive pole, power supply negative pole

2. L+ load positive pole, L- load negative pole

3. Forbid to connect power positive and negative pole inversely.

4. Rated voltage:

1P: 250V;2P: 500V;

3P: 750V;4P: 1000V.

Overall and Installation Dimensions

11
12

Ordering Notice

◆ Product model number and name, e.g: PSDX7-63Z (H) DC miniature circuit breaker.

◆ Instantaneous release type and rated current, e.g: C20.

◆ Rated voltage, e.g: DC500V

◆ Ordering number, e.g: 500 sets

◆ Ordering example: PSDX7-63Z(H)/20A DC500V, 500sets


  • Previous:
  • Next:

  • Write your message here and send it to us