CJX1(3TF) Series AC Contactors

Short Description:

Application

CJX1(3TF) Series AC Contactors are suitable for frequency of 50/60Hz. rated insulation voltage up to 690-1000V, rated operational current to 9A-475A at rated operational voltage up to 380V under the utilization category AC-3. They are mainly used for making, breaking electric circuits at a long distance and for frequent starting, stopping and reversing control of AC motos. They comply with IEC947, VDE0660, GB14048.


Product Detail

Product Tags

Specifications

Type CJX1-9F

3TF30

CJX1-9

3TF40

CJX1-12F

3TF31

CJX1-12

3TF41

CJX1-16F

3TF32

CJX1-16

3TF42

CJX1-22F

3TF33

CJX1-22

3TF43

Rated insulation voltage(V) 690 690 690 690 690 690 690 690
 (380V)(A) Rated operational current AC-3 9 9 12 12 16 16 22 22
AC-4 3.3 3.3 4.3 4.3 7.7 7.7 8.5 8.5
 (kW) Rated outputs of three-phase motors at 50Hz AC-3 230/220V 2.4 2.4 3.3 3.3 4 4 5.5 5.5
400/380V 4 4 5.5 5.5 7.5 7.5 11 11
500V 5.5 5.5 7.5 7.5 9 9 11 11
690/660 5.5 5.5 7,5 7.5 11 11 11 11
1000V - - - - - - - -
AC-4 400/380V 1.48/1.4 1.48/1.4 2/9 2/9 3.5 3.5 4 4
690/660V 2.54/2.4 2.54/2.4 3.45/3.3 3.45/3.3 6 6 6.6 6.6
 (*10e) Mechanical endurance 15 15 15 15 15 15 15 15
Electrical endurance AC-3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
AC-4 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
 (1/h)

Switching frequency

AC-3 1000 1000 1000 1000 750 750 750 750
AC-4 250 250 250 250 250 250 250 250
Coil voltage tolerance (0.8-1.1)Us
 (AC) Power consumotion of coil (50Hz)  (VA)/Closed 10 10 10 10 10 10 10 10
p.f. 0.29 0.29 0.29 0.29 0.29 0.29 0.29 0.29
 (VA)/Closed 68 68 68 68 68 68 68 68
P.f. 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82
 (A) Convention althermal current 20 20 20 20 30 30 30 30
 (A)

Conventional thermal current of anxiliary contacts

10 10 10 10 10 10 10 10
 (A) Rated operational current of anxiliary contacts

AC-15

380/220V

4/6 6/10 4/6 6/10 4/6 6/10 4/6 6/10
 (kg) Weight AC0.37 AC0.43 AC0.37 AC0.43 AC0.45 AC0.49 AC0.45 AC0.49

product-description1

Specifications

Type CJX1-32F

3TF34

CJX1-32

3TF44

CJX1-38F

3TF35

CJX1-38

3TF45

CJX1-45

3TF46

CJX1-63

3TF47

CJX1-75

3TF48

CJX1-85

3TF49

 (V) Rated insulation voltage

690

690 690 690 1000 1000 1000 1000
 (380V)(A) Rated operational current AC-3 32 32 38 38 45 63 75 85
AC-4 15.6 15.6 18.5 18.5 24 28 34 42
 (kW) Rated outputs of three-phase motors at 50Hz AC-3 230/220V 8.5 8.5 11 11 15 18.5 22 26
400/380V 15 15 18.5 18.5 22 30 37 45
500V 21 21 25 25 30 41 50 59
690/660 23 23 23 23 39 55 67 67
1000V - - - - - - 39 39
AC-4 400/380V 7.5 7.5 9 9 12.6/12 14.7/14 17.9/17 22/21
690/660V 13 13 15.5 15.5 21.8/20.8 25.4/24.3 30.9/29.5 38/36
 (*10c) Mechanical endurance 10 10 10 10 10 10 10 10
 (MO6) Electrical endurance AC-3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
AC-4 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
 (1/h) Switching frequency AC-3 750 750 600 600 1200 1000 1000 850
AC-4 250 250 200 200 400 300 300 250
Coil voltage tolerance (0.8-1.1)Us
 (AC) Power consumotion of coil (50Hz) (VA)/Closed 12.1 12.1 12.1 12.1 17 17 32 32
p.f. 0.28 0.28 0.28 0.28 0.29 0.29 0.29 0.29
 (VA)/Closed 101 101 101 101 183 183 330 330
P.f. 0.83 0.83 0.83 0.83 0.6 0.6 0.6 0.6
 (A) Convention althermal current 55 55 55 55 80 90 100 100
 (A)

Conventional thermal current of anxiliary contacts

10 10 10 10 10 10 10 10
 (A) Rated operational current of anxiliary contacts AC-15

380/220V

4/6 4/6 4/6 4/6 4/6 4/6 4/6 4/6
(kg) Weight AC0.68 AC0.8 AC0.68 AC0.8 AC1.4/1.6 AC1.4/1.6 AC2.3/2.5 AC2.3/2.5

product-description2

Specifications

Type CJX1-110

3TF50

CJX1-140

3TF51

CJX1-170

3TF52

CJX1-205

3TF53

CJX1-250

3TF54

CJX1-300

3TF55

CJX1-400

3TF56

 (V) Rated insulation voltage 1000 1000 1000 1000 1000 1000 1000
 (380V)(A) Rated operational current AC-3 110 140 170 205 250 300 400
AC-4 54 68 75 96 110 125 150
 (kW) Rated outputs of three-phase motors at 50Hz AC-3 230/220V 37 43 55 64 78 93 125
400/380V 55 75 90 110 132 160 200
500V 76 98 118 145 178 210 184
690/660 100 100 156 156 235 235 375
1000V 65 65 90 90 132 132 250
AC-4 400/380V 28.4/27 36/35 40/38 52/50 61/58 69/66 85/81
690/660V 49/56.9 63/60 69/66 90-86 105/100 119-114 147/140
 (*10c) Mechanical endurance 10 10 10 10 10 10 10
C10e) Electrical endurance AC-3 1.2 1.2 1.2 1.2 1.2 1.2 1.2
AC-4 0.2 0.2 0.2 0.2 0.2 0.2 0.2
 (1/h) Switching frequency AC-3 1000 750 700 500 700 500 500
AC-4 300 200 200 130 200 130 150
Coil voltage tolerance (0.8-1.1)Us
 (AC) Power consumotion of coil (50Hz)  (VA)/Closed 39 39 58 58 84 84 115
p.f. 0.24 0.24 0.26 0.26 0.24 0.24 0.33
 (VA)/Closed 550 550 910 910 1430 1430 2450
P.f. 0.45 0.45 0.38 0.38 0.34 0.34 0.21
 (A) Convention althermal current 160 160 210 210 300 300 400
 (A)

Conventional thermal current of anxiliary contacts

10 10 10 10 10 10 10
 (A) Rated operational current of anxiliary contacts

AC-15

380/220V

4/6 4/6 4/6 4/6 4/6 4/6 4/6
(kg) Weight AC3.3/3.5 AC3.3/3.5 AC3.3/3.5 AC3.3/3.5 AC6.2/6.4 AC6.2/6.4 AC8.5/8.7

  • Previous:
  • Next:

  • Write your message here and send it to us